Category: Technical information associated with EllisonAC Benefits
of Packaged Plant Rooms Specification of Packaged Plant Rooms
Email EllisonAC
EllisonAC Limited Benefits & Specification of Packaged Plant
Rooms
Benefits of Using & Specifying EllisonAC Packaged Plant Rooms
- Design & fabrication is carried out totally in house
- Consultancy & management time together with the associated costs
are significantly reduced
- Patented acoustic vented ridge for optimum temperature control
- Patented method of fixing cladding panels giving a homogenous
finish
- Concealed gutters& downspouts
- Insulated floor preventing underfloor condensation & corrosion
- Integrated electrical containment system
- Removable cladding panels
- Modular units extendable by 1172mm panels
- Integral floor drainage
- Acoustic and non-acoustic units
- Delivery & installation normally carried out within 1 working
day
- The delivery will not have an effect on the critical path of the
programme, as in-built plant has
- The units can be fully tested, pre-commissioned & witnessed off
site
- Delivery time is normally 8-10 weeks from approval of drawings
Specification for EllisonAC Packaged Plant Roms
General
The container shall be manufactured by EllisonAC, provided with
adequate means for lifting and positioning into final position utilising
suitable cranage.
Construction
The container shall be a double skinned insulated one-piece unit
constructed to be capable of accommodating the full operating load of
the installed equipment / installations (both point loads and uniformly
distributed loads).
Walls
External walls are to be constructed of steel panels, complete with
adequate steel vertical supporting members at suitable centres. Heavy
duty galvanised channel 41mm x 41mm x 2mm gap and 6mm return to be
provided within each supporting member for pipework support and
electrical containment systems as required.
External Finish
The steelwork frame to be generally painted with two coats air drying
enamel to Colour Code BS.10A05 Goosewing Grey or equal.
Internal Finish
The steelwork frame to be as above. Silicone type sealant to be
applied to panel joints where a weatherproof / air seal is required.
External/Internal Panels
Option A – Bonded Panels (also available as fire rated)
The walls shall be preformed removable panels manufactured from
Plastisol coated steel sheeting, and shall be 40mm thick zero ODP slab
insulation.
Internally the panels will have bright white liner enamel affixed,
encasing the whole panel.
Option B – Acoustic Panels (also available as fire rated)
The walls shall be preformed removable panels manufactured from
Plastisol coated steel sheeting, and shall be 80mm thick rockwool
insulation.
Internally the panels will have a galvanised perforated sheet fixed with
a glass fibre tissue membrane to prevent migration of the insulation.
Option C – Bonded/Acoustic Panels (also available as fire rated)
The walls shall be preformed removable panels manufactured from
Plastisol coated steel sheeting, and shall be an 80mm thick combination
panel of 40mm thick zero ODP slab insulation and 40mm thick rockwool
insulation.
Internally the panels will have a galvanised perforated sheet fixed with
a glass fibre tissue membrane to prevent migration of the insulation.
All of the above cladding panels shall be affixed to the container from
the outside thus allowing them to be removable should they be damaged or
for plant replacement. Patent No. 2280206. All joints should have cover
strips fitted, manufactured from the same materials as the external
finish thus ensuring the unit has a homogeneous finish.
Roof
The roof shall be pitched from the central ridge, and shall be double
skin, of steel construction, insulated to maintain minimum thermal
transmittance. Roof finish to be same as walls (option A, B or C). Eaves
to overhang walls. Guttering and downpipes shall be concealed type,
manufactured from plastisol in the same colour as the unit.
Sub-Floor
Generally for container up to a gross weight of 20 tonnes the
sub-floor and floor shall be as follows. All steel shall receive a coat
of weldable primer. Shall be channel with the U-section of the channel
facing all internal elevations. At 1M centres through the length of the
container channel shall be fitted and run from side to side. All
channels shall be fully weld prepped and receive 2 welds to all joints
and butt joints. Running from end to end of the container shall be 2
sections of 100 x 100 angle which shall be weld prepped and fully
welded.
Floor
On the floor shall be laid 4.5mm thick durbar plate and shall have no
more than 4 joints throughout the total floor area. The durbar plate
shall be welded to the sub-floor by stitch welding and there shall be a
minimum of 20% of the steel contact area of the floor to the sub-base
welded. All joints within the floor area shall be fully welded and prior
to welding have been levelled from beneath to prevent ponding of water.
A 200 x 4.5mm durbar kicker plate shall be welded to the completed floor
to prevent damage to the container side panels. After the welding of the
kicker plate the container shall be tested for leakage.
The completed floor shall receive 2-No. coats of epoxy non-slip semi
matt floor paint to an approved colour. 1-No. coat shall be applied
after completing all site works or commissioning. The sub-floor shall
receive 2-No. coats of black bituminous paint applied by airless spray
to ensure even coat to all steelwork.
Underfloor Insulation
To all the sub-floor area foil faced insulation board shall be
affixed thus ensuring no underfloor condensation will form resulting in
corrosion to the underfloor steelwork taking place.
Where entry point is requested through the floor, a 200mm high upstand
detail can be provided, matching the general 200mm high skirting
throughout the container.
Internal Drainage
Drainage will take place through the door thresholds out onto the
roof area, or through an alternatively specified drain gully.
Doors
Outwards opening steel doors are to be provided as requested and hung
on stainless steel security pattern hinges. Suitably designed internal
door stays are also to be fitted and door clips to hold the doors back
fully, if required. The minimum door opening is to be 1M wide x 2M high
and is to be sized to facilitate removal of major plant/equipment items.
All doors to be constructed and insulated to the same thermal
transmittance value as the container walls. A security lock is to be
fitted.
Internal Plinths/Bases
Suitably designed pump plinths / bases can be provided where
required, to comply with the requirements of equipment manufacturers.
Where bases are provided, they shall make all necessary provision to
isolate vibration / noise transmission as required.
Technical information associated with: Ellison - Packaged Plant, Mobile
Boiler Hire, Containerised Plantroom Solutions
|