1 Supply a Vapac VapaNet self-contained, electronically controlled,
self-generating wall mounted electrode boiler type steam generator.
Nominate a) VapaNet LE- On / Off Control
b) VapaNet LE- Water Level Control
c) VapaNet LE-P Pulsed Energy Control
Each humidifier uses electrode boiler technology and is capable of
producing - kg/hr of steam at atmospheric pressure.
2 The internal control circuit within the humidifier shall be 24V a.c.
The internal control PCB is 9V a.c. The drain pumps are 230V a.c.
powered from the internal primary transformer.
3 The steam shall be produced at atmospheric pressure in a polypropylene
cylinder, the material of which shall be bio degradable and able to be
recycled. The steam connection from each cylinder shall be 35mm or 55mm
dependant on the nominated model.
a) The cylinder is a disposable, all-welded manufacture incorporating
specially constructed electrodes housed within.
b) The cylinder is a splittable, clamped construction incorporating
specially constructed electrodes housed within.
4 The humidifier includes a 240V a.c. drain pump that shall be used to
drain the cylinder for anti-foam protection and normal drainage cycles.
The pump is housed underneath the base drain pan of the mechanical
compartment, and discharges at a maximum rate of 16.8 l/min at 50Hz
power supply (17.2 l/min at 60Hz) per cylinder.
5 The humidifier is configured to accept various power supplies all of
which would enable the humidifier to deliver the nominated capacity.
Voltage: 200, 230, 380, 415, 440.
Supply: Single phase plus neutral, Two phase, Three phase.
6 The Humidifier is a LON Mark control device and can communicate with
any proprietary open architecture Building Management System that is
compatible with LON protocols.
The humidifier can accept an externally generated control signal direct
from a sensor or a BMS. The control signal shall be: Potentiometric,
0-5V, 0-10V, 0-20V, 2-10V, 1-18V, 4-20mA, Network.
The controller incorporates volt-free contacts to indicate Unit Run and
Unit Alarm when connected to a suitable interface.
7 The humidifier shall have the capability to introduce safety
interlocks from the air conditioning system such as Fan Interlock. Air
Flow Switch, and High Limit Hygrostat via a dedicated security circuit.
8 The Humidifier has a separated electrical and mechanical section
suitably sealed to prevent spillage leaking. The drain pan is
constructed from 316-grade stainless steel. The body of the cabinet is
constructed from galvanised mild steel finished in a polyester paint to
BS00A05. The cabinet is ventilated to ensure heat generated inside is
suitably dissipated from vents in the back of the top panel. The doors
to the cabinet shall include two positive close locks requiring a key to
open. A key is provided with each unit.
The humidifier incorporates an LED indicator panel to the front
(left-hand) door, showing the user or engineer the operational state of
the system. The LED’s indicate: Unit Off, Unit on line and operational,
Unit on standby, Drain fault, Unit stopped. Feed fault, Unit stopped,
Over current, Service interval expired, Service routine operational,
Service routine completed, Constant output active.
9 To avoid earth leakage, the power supply will be disconnected from the
electrodes when the system is in drain mode.
10 All Humidifiers comply to local and national water and plumbing
codes, and incorporate a fill cup with a 25mm air gap on the water feed
line to prevent back feed and contamination of the water supply line.
The drain circuit discharges through a drain trap vented to the steam
cylinder compartment.
11 The water feed to the Humidifier incorporates a strainer and flow
restrictor to suit connection to water supplies with pressures in the
range 1 to 8 bar.
Options
12a An Alpha-Numeric Display is incorporated into the (left hand)
front door as a factory fitted item to allow password access to three
levels of administration.
User level
Service engineer level
Systems engineer level
12b An Alpha-Numeric Display is incorporated into a separate box
complete with a two metre lead and plug to allow remote mounting of the
display. This display can be permanently mounted or used as a service
tool and disconnected from the apparatus after completion of work.
13 A three metre communication cable is available for master / slave
operation. The cable has factory fitted plugs to each end of ease of
connection.
14 A Room Distribution Unit mounted directly onto the Humidifier cabinet
is available for all single cylinder models, 05, 09, 18, 30, 45. The
same Room Distribution Unit can be mounted remotely from cabinet and
steam lines, and power cabling can be run between.
Dimensions & Weights

|