Eaton-Williams
Humidifier Guide Specification
1 Supply a Vapac VapaNet self-contained,
electronically controlled, self-generating wall mounted electrode
boiler type steam generator.
Nominate a) VapaNet LE- On / Off Control
b) VapaNet LE- Water Level Control
c) VapaNet LE-P Pulsed Energy Control
Each humidifier uses electrode boiler technology and is capable of
producing - kg/hr of steam at atmospheric pressure.
2 The internal control circuit within the humidifier shall be 24V
a.c. The internal control PCB is 9V a.c. The drain pumps are 230V
a.c. powered from the internal primary transformer.
3 The steam shall be produced at atmospheric pressure in a
polypropylene cylinder, the material of which shall be biodegradable
and able to be recycled. The steam connection from each cylinder
shall be 35mm or 55mm dependant on the nominated model.
a) The cylinder is a disposable, all-welded manufacture
incorporating specially constructed electrodes housed within.
b) The cylinder is a splittable, clamped construction incorporating
specially constructed electrodes housed within.
4 The humidifier includes a 240V a.c. drain pump that shall be used
to drain the cylinder for anti-foam protection and normal drainage
cycles. The pump is housed underneath the base drain pan of the
mechanical compartment, and discharges at a maximum rate of 16.8
l/min at 50Hz power supply (17.2 l/min at 60Hz) per cylinder.
5 The humidifier is configured to accept various power supplies all
of which would enable the humidifier to deliver the nominated
capacity.
Voltage: 200, 230, 380, 415, 440.
Supply: Single phase plus neutral, Two phase, Three phase.
6 The Humidifier is a LON Mark control device and can communicate
with any proprietary open architecture Building Management System
that is compatible with LON protocols.
The humidifier can accept an externally generated control signal
direct from a sensor or a BMS. The control signal shall be:
Potentiometric, 0-5V, 0-10V, 0-20V, 2-10V, 1-18V, 4-20mA, Network.
The controller incorporates volt-free contacts to indicate Unit Run
and Unit Alarm when connected to a suitable interface.
7 The humidifier shall have the capability to introduce safety
interlocks from the air conditioning system such as Fan Interlock,
Air Flow Switch, and High Limit Hygrostat via a dedicated security
circuit.
8 The Humidifier has a separated electrical and mechanical section
suitably sealed to prevent spillage leaking. The drain pan is
constructed from 316-grade stainless steel. The body of the cabinet
is constructed from galvanised mild steel finished in a polyester
paint to BS00A05. The cabinet is ventilated to ensure heat generated
inside is suitably dissipated from vents in the back of the top
panel. The doors to the cabinet shall include two positive close
locks requiring a key to open. A key is provided with each unit.
The humidifier incorporates an LED indicator panel to the front
(left-hand) door, showing the user or engineer the operational state
of the system. The LED’s indicate: Unit off, Unit on line and
operational, Unit on standby, Drain fault, Unit stopped, Feed fault,
Unit stopped, Over current, Service interval expired, Service
routine operational, Service routine completed, Constant output
active.
9 To avoid earth leakage, the power supply will be disconnected from
the electrodes when the system is in drain mode.
10 All Humidifiers comply to local and national water and plumbing
codes, and incorporate a fill cup with a 25mm air gap on the water
feed line to prevent back feed and contamination of the water supply
line. The drain circuit discharges through a drain trap vented to
the steam cylinder compartment.
11 The water feed to the Humidifier incorporates a strainer and flow
restrictor to suit connection to water supplies with pressures in
the range 1 to 8 bar.
Options
12a An Alpha-Numeric Display is incorporated into the (left hand)
front door as a factory fitted item to allow password access to
three levels of administration.
User level
Service engineer level
Systems engineer level
12b An Alpha-Numeric Display is incorporated into a separate box
complete with a two metre lead and plug to allow remote mounting of
the display. This display can be permanently mounted or used as a
service tool and disconnected from the apparatus after completion of
work.
13 A three metre communication cable is available for master / slave
operation. The cable has factory fitted plugs to each end of ease of
connection.
14 A Room Distribution Unit mounted directly onto the Humidifier
cabinet is available for all single cylinder models, 05, 09, 18, 30,
45. The same Room Distribution Unit can be mounted remotely from
cabinet and steam lines, and power cabling can be run between.
Humidifier Specification - Dimensions & Weights

(Click on image for larger display)
Request information:
Colman Moducel Eaton Williams
grilles diffusers louvres air handling fan coil units
Request information:
Eaton Williams steam humidifier
gas fired steam humidifiers data room cooling vapac
Request information:
Colman Moducel building louvres
external louvres ventilation Colman Moducel
Technical information associated with:
Colman
Moducel Energy Saving Data Centre Cooling Cooling Distribution
Technical information associated with:
Colman Moducel performance louvres external ventilation louvres external
grilles
|

Eaton-Williams Group
Fircroft Way
Edenbridge
Kent
TN8 6EZ
Email this company
Tel : 01732 866055
Fax : 01732 869626

|