- BuildingDesign - Services & Construction Products Index
Cast-Resin Insulated Copper Aluminium Busduct
![]()
The betobar-r busbars can be supplied in the following standard types:
For Low voltage Bus Bars
Up to 1000 V AC 45-55 Hz – three phase conductors and/or:
Protective earth 50, 100, 150 and 200% neutral
Alu-conductors range up to 5250 Amps
Cu-conductors range up to 6500 Amps
For DC applications up to 16.000 Amps and 1500 V DC
To IEC-439-2
400 to 6500 Amps – 1000v
Models with 3 phase – 3-wire and 4-wire with full size neutral and earth conductor
For Medium Voltage Bus Bars
Type Current rating Voltage rating
SH up to 2000 A up to 7.2 kV
PH up to 3600 A up to 17.5 kV
MH up to 5000 A up to 24.0 kV
To IEC-466
800 A to 6300 Amps
In compact types for 3,6 – 7,2 – 12 and 17,5 kV also with segregated phases for 24 kV generator busbars
Other current ratings on request.
Test
Type tests
All technical data specified, such as current ratings and temperature rise, insulation resistance, voltage and short circuit withstand, have been certified in accordance with international standards (IEC, VDE or BS) by the independent testing stations K.E.M.A., LABORELEC, LCIE. Assembled elements with cast junctions were submitted for type testing.
Applications for:
Low Voltage Busbar
Medium Voltage Busbar


![]()