Static Transfer Systems Product Data
Socomec UPS - Static Transfer Systems Product Data
Static Transfer UPS Systems - Operating Specifications - Technical Output Data
Secure Power for Guaranteed Business Continuity
Mission-critical applications require a highly available power supply. The SOCOMEC UPS Static Transfer System (STS), STATYS, provides the highest availability values of permanent power supply, essential for service continuity.
STATYS protects against:
- Main power outages
- Operator errors
- Failures in the upstream power distribution system
- Failures caused by faulty equipment supplied by the same source
User benefits of Static Transfer Systems:
- Provides redundant power supply to mission
- Increases the power availability by choosing the best quality supply
- Prevents fault propagation
- Optimises the use of the power sources during load transients
- Facilitates infrastructure maintenance without application shutdown
- Allows easy extension and infrastructure design of the architecture
In addition, UPS STATYS offers the following benefits:
- Minimal heat dissipation
- High short circuit capability
- Clear and easy to use human interface
- Full internal redundancy for maximum fault tolerance
- Fast and easy front access to every internal component
- Independent source management
- Wide range of communication protocols management
- Full compliance to the latest standards and CBEMA / ITIC recommendations for critical loads
Flexibility and adaptability, STATYS is designed to provide:
- Redundancy from two alternative and independent power sources
- Instantaneous manual and automatic transfer
- Selection of preferred source by the operator
- Programmable re-transfer after an automatic transfer
- Programmable automatic restart
- All pole switching possibilities to keep source fully separated providing compatibility with all types of earthing systems
- Easy operating thanks to a comprehensive control panel with mimic diagram and display
- Fast output fault current sensing, preventing the transfer of the faulty equipment to the opposite circuit. Disturbances such as short-circuits on any other equipment can be avoided
- Double interlocked maintenance bypass
- Comprehensive communication facility, SNMP, JBUS/MODBUS, HTTP
- Ethernet connection to a LAN connection for remote monitoring by the customer (MODBUS TCP)
- Tele-maintenance connection
Transfers: Switching mode
Depending on the source state, the transfers can be either synchronous or asynchronous. The switching operation is extremely fast and secured and is a “break before make” transfer.
The two sources are never cross connected, thus avoiding any risk of overlapping of power sources during transfer.
Backfeed protection
To be compliant with the standard IEC 62310-1, STATYS is fitted with a “backfeed” protection system to protect against possible voltage backfeed to one source (integrated for single phase).
STATYS
- Redundant micro-controller board
- Dual redundant electronic power
- Independent SCR - with redundant local power supply
Operating Specifications

Rack and Cabinet integrated only; For OEM Chassis: dedicated inputs are available for the external switches management

Rack/Cabinet & OEM Chassis versions

*@ 100% linear with 415V inputs / *@ 100% linear with 415V inputs on PDU Integral versions (as per 6230-3 Standard)