Category: Siemens Barduct Busbar Systems Busbar Typical
Specification Clauses
Email Siemens Barduct
Siemens Barduct Busbar Systems / Typical Specification Clauses
CDK Lighting Trunking
The following is intended as a guide to specifying CD lighting
trunking:
All lighting busbar trunking shall be approved manufacture and comply
with degree of protection IP54 as defined in BSEN 60439. The current
rating shall be defined on the drawings and schedules but will be
typically 35A, 32A & 40A, 4 pole or 8 pole. The system shall be totally
enclosed. The trunking shall be suitable for use on a 400V 1, 2, 3, 4
phase (2, 3, 4 wire; PE = housing), 50/60 Hz supply and for the
installation to meet the requirements of the IEE Wiring Regulations BS
7671 and BSEN 60439 parts 1 & 2. The enclosure shall be manufactured
from zinc coated sheet steel, finished in white (similar to RAL 9002),
rectangular in section with flanges to the manufacturers standard
suspension and luminaire support brackets. Phase and neutral conductors
shall be tinned copper of equal cross section, fully insulated and
supported at both the tapping outlet positions and at each end of the
trunking.
The lighting Busbar trunking shall be manufacturers in 2 or 3 metre
lengths each complete with a self-aligning electrical joint sleeve,
interlocked to prevent phase reversal.
Tapping outlet positions shall be provided at 0.5 or 1 metre lengths
each complete with a non removable hinged cover complete with locking
screw to ensure IP54 rating and preventing accidental contact with the
live conductors. All end feed units, end caps, joint sleeves and tap off
units shall be manufactured from non-hygroscopic, self-extinguishing
halogen-free insulating material and designed such that IP54 degree of
protection is maintained.
Tap-off Units
Tap-offs shall be rated at 10A or 16A, 3 pole or 5 pole as defined on
the drawings and schedules. They shall be plug-in and designed so as to
permit phase selection on site by inserting of prewired contact blocks
into the appropriate positions. Fused or unfused tap-off units shall be
provided as required. The lighting trunking shall be Siemens CDK,
Barduct brand or equal and approved.
BD01 Busbar Trunking
The following is intended as a guide to specifying BD01 busbar
trunking:
All busbar trunking shall be of approved manufacturing and comply with
degree of protection IP54 as defined in BSEN 60439 when edgewise
(tap-off points at the side and bottom) and IP50 when flat (tap-off
points on the top). The current rating shall be defined on the drawings
and schedules but will be typically 40A to 160A. The busbar shall be
designed and manufactured to comply with BSEN 60439 parts1 and 2. For
use on a 400V, 3 phase 4 wire (PE = Housing), 50/60Hz supply, and
capable of withstanding prospective fault levels as detailed on the
drawing schedules. The busbar trunking shall be manufactured in 2 or 3
metre lengths. The enclosure shall be manufactured from pale grey (RAL
7035) painted galvanised sheet steel and is the protective earth
conductor. The busbar trunking shall have solid conductors with
silver-plated aluminium and copper connection points at all tap-off
outlets and joint positions. Tap-off outlets shall be spaced at 0.5 and
1 metre distance and shall have automatic opening and closing shutters.
They will also ensure correct polarity is maintained. The joint section
shall provide electrical and mechanical connection by four screws. The
joint section shall absorb any differential expansion between the
trunking and the conductors.
When a change in direction, rating or termination occurs in a busbar
run, manufacturer’s purpose made fittings such as junction units, feeder
units, end flanges and centre feeds shall be used.
Where detailed on the drawings and schedules interlocking coding sets
shall be installed into the tap-off outlets and tap-off units to provide
non-interchange ability of tap-off units to non-designated tap-off
outlets.
Tap-off Units
Tap-off units shall be plug-in type suitable to accept HRC fuses, MCBs,
DIN rail mounted devices and socket outlets as detailed on the drawings
and schedules. The enclosure shall be constructed from anodised
aluminium and/or insulation material, complying to the degree of
protection IP54, as defined in BSEN 60439. The earth connection of the
tap-off unit shall provide the opening of the automatic shutter and make
before and break after the live connections are made. Where required
tap-off units shall be extendible to allow additional components to be
installed onto the internal DIN rail.
The busbar trunking system shall be Siemens BD01, Barduct brand or equal
and approved.
BD2 Busbar Trunking
The following is intended as a guide to specifying BD02 busbar
trunking:
All busbar trunking shall be of approved manufacture and the current
ratings detailed on the drawings and schedules – typically from 160A to
1250A, and complying to degree of ingress protection IP52 defined in
BSEN 60439 and IP54 with accessories. The busbar shall be designed and
manufactured to comply with BSEN 60439 parts 1 and 2. For use on a 690v,
3 phase 5 wire (3L, N of half N, PE or half PE), 50/60Hz supply, and
capable of withstanding prospective fault levels as detailed on the
drawing schedules.
The busbar trunking shall be manufactured in 1.25, 2.25 & 3.25 metre
lengths or optional lengths from 0.5 up to 3.24 metres. The enclosure
shall be manufactured from pale grey (RAL 7035) painted galvanised sheet
steel. The busbar trunking shall have solid conductors with
nickel-plated and tinned aluminium or copper, with insulated tap-off
outlets and busbar supports.
Tap-off outlets shall be spaced at 0.5 and 1 metre distance and shall
have automatic opening and closing shutters. They will also ensure
correct polarity is maintained.
The joint section shall provide electrical and mechanical connection by
four screws. The joint section shall absorb any differential expansion
between the trunking and the conductors.
When a change in direction, rating or termination occurs in a busbar
run, manufacturer’s purpose-made fittings such as L junction units,
feeder units, end flanges and centre feeds shall be used.
When supplied as Rising Main busbar suitable fire barriers must be
fitted which meet the requirements of BSEN 60439 part 2 and of fire
resistance Class S120.
Tap-off Units
Tap-off units shall be plug-in type suitable to accept HRC and BS fuses,
MCBs, MCCBs, Switch Disconnectors, DIN rail mounted devices and socket
outlets as detailed on the drawings and schedules. The enclosure shall
be constructed from painted steel and/or insulation material, complying
to the degree of protection IP54, as defined in BSEN 60439. The earth
connection of the tap-off unit shall be provide the opening of the
automatic shutter and make before and break after the live connections
are made.
Where required, tap-off units shall be extendible to allow additional
components to be installed onto the internal DIN rail.
The busbar trunking system shall be Siemens BD2, Barduct brand or equal
and approved.
LX Busbar Trunking
The following is intended as a guide to specifying LX busbar trunking:
All busbar trunking shall be of approved manufacture and the current
ratings detailed on the drawings and schedules – typically from 800A to
6300A, and complying with degree of ingress protection IP54 defined in
BSEN 60439.
The system shall be totally enclosed and low impedance sandwich
construction. The trunking shall be suitable for use on 690V 50Hz supply
and available in various configurations including 3 phase and Neutral,
double neutral, earth and/or clean earth (with a maximum of six
conductors). It shall meet the requirements of the IEE Wiring
Regulations BS 7671 and BSEN 560439 parts 1 & 2. The enclosure shall be
manufactured from aluminium finished in pale grey RAL 7035, prepared to
accept manufacture’s standard suspension hangers and support brackets.
Phase and neutral conductors shall be nickel and tin plated aluminium,
or copper, of equal cross-section fully insulated.
The busbar trunking current rating must be equal in all installation
positions (flat, edge or vertical). A derating in any position is not
acceptable.
The busbar trunking shall be manufactured in different lengths up to 3
metres either as feeder or distribution busbar. Each plug in joint
located at the end of each busbar length will be equipped with a self-torquing
sheer head single torque bolt joint block. Manufacturers standard
junction units shall be supplied as standard, including elbows, knees,
T-sections, offsets, expansion fittings, and end caps. Further standard
components must be available such as cable feeder boxes, transformer
connections and panel flange connections. For distribution busbar,
tapping outlet positions shall be manufactured from non-hygroscopic
self-extinguishing halogen-free insulating material and designed such
that the IP54 degree of protection is maintained. When supplied as
Rising Main busbar the construction should be suitable to provide fire
barrier protection to meet the requirements of BSEN 60439 past 2 and of
fire resistance Class S120.
Tap-off Units
When supplied as Rising Main busbar suitable fire barriers must be
fitted which meet the requirements of BSEN 60439 part 2 and of fire
resistance Class S120. Tap-off units shall be plug-in type up to 630amps
and fix mounted from 800A to 1250A. Incorrect mounting shall be
prevented by an interlocking mechanism. The tap-off units shall be
equipped with either fused switch or MCCB. The short circuit rating
shall be up to 100kA at 415V 50Hz.
The enclosure shall be constructed from painted steel and/or insulation
material, complying to the degree of protection IP54, as defined in BSEN
60439.
The earth connection of the tap-off unit shall provide the opening of
the automatic shutter, and make before and break after the live
connections are made.
The busbar trunking system shall be Siemens LX, Barduct brand or equal
and approved.
LR Cast Resin Busbar Trunking
The following is intended as a guide to specifying LR Cast Resin
busbar trunking:
All busbar systems shall be of approved manufacture and comply with
degree of protection IP68, as defined in IEC60529. The current ratings
shall be as defined on technical data sheets, drawings and schedules.
The trunking shall be suitable for use up to 1000V 50Hz supply, and
available in 4 and 5 bar versions, and meet the requirements of the IEE
wiring regulations (BS7671) and IEC60439-1 and IEC60439-2. The enclosure
shall be manufactures from an agglomerate of quartz and epoxy. Phase and
Neutral conductors (as well as the internal PE conductor where required)
shall be HDHC copper, of equal cross section.
The busbar must maintain its rated current when mounted in any
installation position (flat, edge or vertical). The single body system
shall cover up to 3150A in a single-conductor single-body construction,
and up top 6300A in a double-conductor single-body construction.
Various junction units shall be supplied as standard, including elbows,
knees, tees and flanged switchboard connections.
The Cast Resin Busbar trunking shall be Siemens LRC range or equal and
approved.
|