Busbar Systems / Typical Specification Clauses

CDK Lighting Trunking

The following is intended as a guide to specifying CD lighting trunking:
All lighting busbar trunking shall be approved manufacture and comply with degree of protection IP54 as defined in BSEN 60439. The current rating shall be defined on the drawings and schedules but will be typically 35A, 32A & 40A, 4 pole or 8 pole. The system shall be totally enclosed. The trunking shall be suitable for use on a 400V 1, 2, 3, 4 phase (2, 3, 4 wire; PE = housing), 50/60 Hz supply and for the installation to meet the requirements of the IEE Wiring Regulations BS 7671 and BSEN 60439 parts 1 & 2. The enclosure shall be manufactured from zinc coated sheet steel, finished in white (similar to RAL 9002), rectangular in section with flanges to the manufacturers standard suspension and luminaire support brackets. Phase and neutral conductors shall be tinned copper of equal cross section, fully insulated and supported at both the tapping outlet positions and at each end of the trunking.
The lighting Busbar trunking shall be manufacturers in 2 or 3 metre lengths each complete with a self-aligning electrical joint sleeve, interlocked to prevent phase reversal.
Tapping outlet positions shall be provided at 0.5 or 1 metre lengths each complete with a non removable hinged cover complete with locking screw to ensure IP54 rating and preventing accidental contact with the live conductors. All end feed units, end caps, joint sleeves and tap off units shall be manufactured from non-hygroscopic, self-extinguishing halogen-free insulating material and designed such that IP54 degree of protection is maintained.

Tap-off Units
Tap-offs shall be rated at 10A or 16A, 3 pole or 5 pole as defined on the drawings and schedules. They shall be plug-in and designed so as to permit phase selection on site by inserting of prewired contact blocks into the appropriate positions. Fused or unfused tap-off units shall be provided as required. The lighting trunking shall be Siemens CDK, Barduct brand or equal and approved.

BD01 Busbar Trunking

The following is intended as a guide to specifying BD01 busbar trunking:
All busbar trunking shall be of approved manufacturing and comply with degree of protection IP54 as defined in BSEN 60439 when edgewise (tap-off points at the side and bottom) and IP50 when flat (tap-off points on the top). The current rating shall be defined on the drawings and schedules but will be typically 40A to 160A. The busbar shall be designed and manufactured to comply with BSEN 60439 parts1 and 2. For use on a 400V, 3 phase 4 wire (PE = Housing), 50/60Hz supply, and capable of withstanding prospective fault levels as detailed on the drawing schedules. The busbar trunking shall be manufactured in 2 or 3 metre lengths. The enclosure shall be manufactured from pale grey (RAL 7035) painted galvanised sheet steel and is the protective earth conductor. The busbar trunking shall have solid conductors with silver-plated aluminium and copper connection points at all tap-off outlets and joint positions. Tap-off outlets shall be spaced at 0.5 and 1 metre distance and shall have automatic opening and closing shutters. They will also ensure correct polarity is maintained. The joint section shall provide electrical and mechanical connection by four screws. The joint section shall absorb any differential expansion between the trunking and the conductors.
When a change in direction, rating or termination occurs in a busbar run, manufacturer’s purpose made fittings such as junction units, feeder units, end flanges and centre feeds shall be used.
Where detailed on the drawings and schedules interlocking coding sets shall be installed into the tap-off outlets and tap-off units to provide non-interchange ability of tap-off units to non-designated tap-off outlets.

Tap-off Units
Tap-off units shall be plug-in type suitable to accept HRC fuses, MCBs, DIN rail mounted devices and socket outlets as detailed on the drawings and schedules. The enclosure shall be constructed from anodised aluminium and/or insulation material, complying to the degree of protection IP54, as defined in BSEN 60439. The earth connection of the tap-off unit shall provide the opening of the automatic shutter and make before and break after the live connections are made. Where required tap-off units shall be extendible to allow additional components to be installed onto the internal DIN rail.
The busbar trunking system shall be Siemens BD01, Barduct brand or equal and approved.

BD2 Busbar Trunking

The following is intended as a guide to specifying BD02 busbar trunking:
All busbar trunking shall be of approved manufacture and the current ratings detailed on the drawings and schedules – typically from 160A to 1250A, and complying to degree of ingress protection IP52 defined in BSEN 60439 and IP54 with accessories. The busbar shall be designed and manufactured to comply with BSEN 60439 parts 1 and 2. For use on a 690v, 3 phase 5 wire (3L, N of half N, PE or half PE), 50/60Hz supply, and capable of withstanding prospective fault levels as detailed on the drawing schedules.
The busbar trunking shall be manufactured in 1.25, 2.25 & 3.25 metre lengths or optional lengths from 0.5 up to 3.24 metres. The enclosure shall be manufactured from pale grey (RAL 7035) painted galvanised sheet steel. The busbar trunking shall have solid conductors with nickel-plated and tinned aluminium or copper, with insulated tap-off outlets and busbar supports.
Tap-off outlets shall be spaced at 0.5 and 1 metre distance and shall have automatic opening and closing shutters. They will also ensure correct polarity is maintained.
The joint section shall provide electrical and mechanical connection by four screws. The joint section shall absorb any differential expansion between the trunking and the conductors.
When a change in direction, rating or termination occurs in a busbar run, manufacturer’s purpose-made fittings such as L junction units, feeder units, end flanges and centre feeds shall be used.
When supplied as Rising Main busbar suitable fire barriers must be fitted which meet the requirements of BSEN 60439 part 2 and of fire resistance Class S120.

Tap-off Units
Tap-off units shall be plug-in type suitable to accept HRC and BS fuses, MCBs, MCCBs, Switch Disconnectors, DIN rail mounted devices and socket outlets as detailed on the drawings and schedules. The enclosure shall be constructed from painted steel and/or insulation material, complying to the degree of protection IP54, as defined in BSEN 60439. The earth connection of the tap-off unit shall be provide the opening of the automatic shutter and make before and break after the live connections are made.
Where required, tap-off units shall be extendible to allow additional components to be installed onto the internal DIN rail.
The busbar trunking system shall be Siemens BD2, Barduct brand or equal and approved.

LX Busbar Trunking

The following is intended as a guide to specifying LX busbar trunking:
All busbar trunking shall be of approved manufacture and the current ratings detailed on the drawings and schedules – typically from 800A to 6300A, and complying with degree of ingress protection IP54 defined in BSEN 60439.
The system shall be totally enclosed and low impedance sandwich construction. The trunking shall be suitable for use on 690V 50Hz supply and available in various configurations including 3 phase and Neutral, double neutral, earth and/or clean earth (with a maximum of six conductors). It shall meet the requirements of the IEE Wiring Regulations BS 7671 and BSEN 560439 parts 1 & 2. The enclosure shall be manufactured from aluminium finished in pale grey RAL 7035, prepared to accept manufacture’s standard suspension hangers and support brackets. Phase and neutral conductors shall be nickel and tin plated aluminium, or copper, of equal cross-section fully insulated.
The busbar trunking current rating must be equal in all installation positions (flat, edge or vertical). A derating in any position is not acceptable.
The busbar trunking shall be manufactured in different lengths up to 3 metres either as feeder or distribution busbar. Each plug in joint located at the end of each busbar length will be equipped with a self-torquing sheer head single torque bolt joint block. Manufacturers standard junction units shall be supplied as standard, including elbows, knees, T-sections, offsets, expansion fittings, and end caps. Further standard components must be available such as cable feeder boxes, transformer connections and panel flange connections. For distribution busbar, tapping outlet positions shall be manufactured from non-hygroscopic self-extinguishing halogen-free insulating material and designed such that the IP54 degree of protection is maintained. When supplied as Rising Main busbar the construction should be suitable to provide fire barrier protection to meet the requirements of BSEN 60439 past 2 and of fire resistance Class S120.

Tap-off Units
When supplied as Rising Main busbar suitable fire barriers must be fitted which meet the requirements of BSEN 60439 part 2 and of fire resistance Class S120. Tap-off units shall be plug-in type up to 630amps and fix mounted from 800A to 1250A. Incorrect mounting shall be prevented by an interlocking mechanism. The tap-off units shall be equipped with either fused switch or MCCB. The short circuit rating shall be up to 100kA at 415V 50Hz.
The enclosure shall be constructed from painted steel and/or insulation material, complying to the degree of protection IP54, as defined in BSEN 60439.
The earth connection of the tap-off unit shall provide the opening of the automatic shutter, and make before and break after the live connections are made.
The busbar trunking system shall be Siemens LX, Barduct brand or equal and approved.

LR Cast Resin Busbar Trunking

The following is intended as a guide to specifying LR Cast Resin busbar trunking:
All busbar systems shall be of approved manufacture and comply with degree of protection IP68, as defined in IEC60529. The current ratings shall be as defined on technical data sheets, drawings and schedules.
The trunking shall be suitable for use up to 1000V 50Hz supply, and available in 4 and 5 bar versions, and meet the requirements of the IEE wiring regulations (BS7671) and IEC60439-1 and IEC60439-2. The enclosure shall be manufactures from an agglomerate of quartz and epoxy. Phase and Neutral conductors (as well as the internal PE conductor where required) shall be HDHC copper, of equal cross section.
The busbar must maintain its rated current when mounted in any installation position (flat, edge or vertical). The single body system shall cover up to 3150A in a single-conductor single-body construction, and up top 6300A in a double-conductor single-body construction.
Various junction units shall be supplied as standard, including elbows, knees, tees and flanged switchboard connections.
The Cast Resin Busbar trunking shall be Siemens LRC range or equal and approved.
 

 

Busbar Typical Specification Clauses

Email this company

Siemens A & D Busbar Sales
Sir William Siemens House
Princess Road
Manchester
M20 2UR


Tel : +44 (0) 161 446 6400
Fax : +44 (0) 161 446 5403

        Request further information:- please provide contact details: For UK and Europe only.
        * Mandatory

*Full Name  
Title  
Enquiry Type    
*Organisation  
*Street Address  
Address (cont.)  
City  
County  
*Postal Code  
*Country  
*Phone  
FAX  
*Email  

        Please provide the project name and/or a short description of your requirements
       *Your Requirements

Validation :
Please type the number shown at the right



Request information above Siemens Barduct Busbar Systems Busbar Typical Specification Clauses

Electrical Services Index

ABB -Packaged sub stations LV switchgear distribution motor control centres

Piller -Static UPS Hybrid Rotary UPS, Diesel Rotary UPS and Static UPS

Electrium Crabtree -Panel Boards MCCB MCB Fuse Switches Distribution

Piller -Hybrid rotary diesel UPS apotrans static transfer switch dual

FKI -Switchgear Hawker Siddeley Switchgear Whipp & Bourne vacuum medium Piller -Static Transfer Switches Static UPS system 3 phase

AVK|SEG -UPS Uninterruptible Power Supplies Digital Static UPS Systems UPS

Ackermann -Underfloor power track floor boxes cable distribution

AVK|SEG -Standby Generation and Maintenance UPS Hire

Sarel -Electrical enclosures wall mounted floor standing rack steel grp

Merlin Gerin -MV switchgear ringmain unit transformers package substations

Abacus -External floodlighting lighting columns road amenity lighting

Merlin Gerin -MV transformers shielded fusegear feeder pillar packaged

Eta-com -Cast-resin insulated busduct copper aluminium cast-resin bu

Hitzinger -Airport ground power diesel driven GPU centralised 400 hz airport

AF Switchgear -LV switchgear  LV Switchboards PDU Switchgear

HITEC -Dual output rotary diesel UPS diesel rotary UPS HITEC

Electropatent -Underfloor track voice and data track floor outlet boxes

HITEC -UPS rotary diesel dual output

Barduct -Busbar Siemens A&D lighting busbars cast resin busbars

Artemide -Architectural lighting - Interior lighting designer light fittings

Hitzinger -Dynamic Diesel Rotary UPS DRUPS Uninterruptible Power

Lucy -Switchgear MV Distribution Switchgear Automation Sabre Vacuum Circuit

Prysmian -Pirelli fire resistant cables FP xlpe armoured cables

HVMS -High Voltage Engineering Solutions fault level services discrimination

Hager -Consumer Units Distribution Boards Klik Modular Plug and

Power Capacitors -Power factor correction equipment Capacitor Maintenance

Profile -Lighting purpose built luminaires low brightness recessed louvr

Luxonic -Lighting Controls Commercial Lighting Dali Lighting Controls

Riegens -Lighting LG3 recessed luminaires surface mounted suspend

Eta-com -Cast resin insulated busbars Eta-com building design cast-resin

OSRAM -Fluorescent electronic control gear lighting control system

G&M Power -Countryman stand-by generators stand-by power marine

Lumitron -Office lighting controls commercial office light fittings industr

GE Power -LV Switchgear motor control centres switchboards distribution

Emergi-Lite -Emergency Lighting Self Contained Luminaires Central

 

| Building Design HomeRequest information | Discussion Help | Terms of Use | Links | News |
| Architectural CPD Seminar Index | HVAC CPD Seminar Index | Electrical CPD Seminar Index |
| Architectural Technical Pages index | Electrical Technical Pages index | Mechanical Technical index

| F1 | F2 | F3 | F4 | F5| A1 | A2 | A3 | A4 | A5 | Architectural Products | HVAC Products | Electrical Products |

Useful building design and construction links -
Abacus Construction Index - Recommended websites for the UK construction industry
Sapling.info - The Architecture, Planning and Landscape Information Gateway
Lighting Directory - Comprehensive lighting information


Recruitment -
Architect Jobs Electrical Engineer Jobs Building Engineering Jobs AutoCad Operator Jobs Structural Engineer Jobs