Profile Lighting Building Regulations - Effect on Lighting
Design
BUILDING REGULATIONS Part L2A - (New Buildings Other Than Dwellings)
- Summary
The intention of these Approved Documents is to introduce measures
which will focus the design in relation to energy conservation. In all
cases, the building will have a PREDICTED rate of carbon emission and a
TARGET rate. The predicted must not exceed the target. The design team
will have to use a standard modelling device to ratify the performance
of the building.
Part L2A
The effect on lighting is summarised below, it covers general
lighting efficacy targets in office, industrial and storage areas in all
building types. (Offices encompass all desk based tasks including school
classrooms, seminar and conference rooms).
Target Initial Efficacy (TIE):- 45 luminaire-lumens/circuit-watt minimum
over whole area.

Another way of considering the calculation is to compare the LOR of an
individual luminaire to the LOR which would be needed to achieve the
proscribed minimum efficacy (see typical tables below). Provided the
luminaire has an LOR greater than that tabulated for the lamp
configuration, then the scheme would comply.

Examples of LOR that meet TIE criteria of 45, 50 & 55 ll/cw with HF
gear
TL5 Lamps

TLD Triphosphor Lamps

TCL Lamps

TCD/TCT Lamps

|