UPS Dual Output Design Guide
Introduction
The Dual Output Diesel UPS system is
designed to replace the traditional Standby Diesel, Static/Rotary
UPS and battery configuration.
By rating the diesel engine and alternator to supply the total site
loads the system can provide the UPS requirements on a continuous
basis, while allowing the standby loads to be re-connected within a
few seconds of any Mains failure.
The Dual Output System can then effectively perform the functions of
both UPS and genset within one integrated unit, which can release
the space traditionally required for the central static/rotary
UPS, batteries, switchgear and associated air conditioning
equipment. This can represent up to 60% of the overall space
allocated for the service requirements. Technical
Data
UPS Overload capacity - 110% for 1 hr per 10h
During normal operation - 125% for 5 min
Without switching to bypass - 150% for 1 min
Input
Input voltage - 380 - 415V, 50Hz
380, 440-480, 600V 60Hz
also MV up to 33kV
Voltage tolerance ± 10%
CosØ at rated voltage 0.98 Output
Output voltage - 380-415V, 50Hz
380, 440-480, 600V 60Hz
also MV up to 33kV
Voltage tolerance steady state ± 1%
Dynamic state ± 5 -10% (depending on system configuration)
During 50 - 250 mS (depending on system configuration)
Frequency tolerance ± 1%
Voltage asymmetry - Max 2%
Harmonic distortion with linear & non linear load Max - 5%
Power factor - 0.8
Short circuit capacity - 15 x rated current
Efficiency up to 97% (depending on System configuration)
Degree of protection Power modules - IP21 (max IP23)
Equipment Cabinets - IP21 (max IP33)
RFI suppression class - EN50 081-2
EN50 082-2
EMC suppression - IEC 1000 Environmental
Conditions
Operational altitude 150m above sea level
Ambient temperature 0 - +40ºC
Relative humidity Max 70% Fuse Clearing
Capabilities
Each Hitec Dual Output UPS Sytem has the ability
to clear fuses of up to 100% of the UPS output whilst maintaining
the output voltage within the specified tolerances.
Input Harmonics
The Hitec Dual Output Diesel system does not
incorporate an input rectifier as with static systems therefore the
reflected harmonics onto the mains utility are negligible and within
the requirements outlined in the Electricity Association’s
regulations G5/4. Load Harmonics
The Hitec Dual Output Diesel system is a low
impedance source and is therefore able to supply non linear loads
without de-rating or the addition of filters.
Selection of Available Models (Other models are available - please
call for details).

(Click on image for larger view)

Request information Hitec - Dual output
rotary diesel UPS diesel rotary UPS HITEC
Request information Hitec - UPS rotary
diesel dual output
Technical information associated with:
Hitec Power Protection Ltd UPS - Dual Output Design Guide