Rating Definitions
Prime Power (models with suffix “P”)
All ratings are suitable for continuous electrical power (at variable
load in lieu of main power network).There are no limitations to the
annual hours of operation and all models can supply 10% overload power
for 1 hour in 12 hours
Standby Power (models with suffix “S”)
Standby ratings are for the supply of emergency power at variable load
in the event of a main powernetwork failure for a limited number of
hours per year. No overloads permitted
For base load (COP) power applications, consult Broadcrown Sales
Department.
Standby Reference Conditions
Output ratings are typical for open sets operating at 380V - 415V (3
phase) and 220V - 240V (single phase)
Ratings at 0.8p.f 25ºC (77ºF) ambient, 177m (600ft) above sea level
All data in accordance with BS5514, ISO 3046, DIN6271, ISO 8528
Wet = with lube oil, coolant and full fuel tank. Dry = with lube oil
Specifications and data subject to change without notice.
Note: Single phase upto 100kVA and 60Hz generating sets are available on
request.
|