Category: Broadcrown Standby Generators Technical Data 1
Email Broadcrown
Broadcrown Standby Generators Technical Data 1

*New engine range these figures to be confirmed **EPA approved engine
(60Hz only) Rating Definitions – BCL Models
All ratings are suitable for continuous electrical power (at variable
load). There are no limitations
to the annual hours of operation. No standby ratings available.
For base load (continuous power) applications. consult Broadcrown Sales
Dept. Rating Definitions – BCJD Models
Prime Power (models with suffix ‘P’).
All ratings are suitable for continuous electrical power (at variable
load in lieu of main power network).
There are no limitation to the annual hours of operation and all models
can supply 10% overloaded power for 1 hour in 12 hours. Standby Power
(models with suffix ‘S’)
Standby ratings are for the supply of emergency power at variable
load in the event of main
power network failure up to a maximum of 500 hours per year. No
overloads permitted. Stand Reference Conditions
Output ratings are typical for sets operating at 380-416V (3 phase)
Ratings at 0.8p.f. 25°C (77°F) ambient, 177m (600ft) above sea level.
All data in accordance with BS5514, ISO3046, DIN6271, ISO8528.
Wet weights = with lube oil and coolant. Dry weights = with lube oil
Specifications and design subject to change without notice


Information associated with: Broadcrown - Diesel & Gas Generators &
Standby Power |